Data logger & Input modules

The SenseAnywhere AiroSensor data logger with input module compatibility

The AiroSensor leads a new generation of ultra low power, wireless temperature data loggers, the 20-20-43 model uses a SAB interface to allow users to connect external sensors and input modules. This allows users to access all of the benefits of the SenseAnywhere data logging system and SAClient software.

The SenseAnywhere AiroSensor X ER model 20-20-43 has an IP67 class connector featuring the digital SenseAnywhere Bus (SAB). The SAB is a hot pluggable interface which provides power and data communication to SAB external sensors from SenseAnywhere. Using this interface means the external sensors can be tested and calibrated as an individual device which provides a huge advantage over analogue interfaces where both the sensor and logging device need to be calibrated as a pair.

The data logger supports various external sensors including CO2, temperature, humidity and temperature, 0-10v and 4-20mA input modules. This allows users to get all of the benefits of the SenseAnywhere logging system and SAClient cloud software. The easy to use, robust, wireless loggers are set up in under 10 minutes, offer a 10-year battery life and do not require 'backing up'. Alarm settings can be easily set to suit individual requirements and provide instant warnings via Email or SMS. SAClient provides simple reporting and quality compliance is a breeze using the intuitive, free software and report templates .

CO2

Temperature & Humidity

0-10V

4-20mA

Key benefits of the logger & input module system include:

  • Connect varioius external sensor types and reap the benefits of the SAClient software
  • Secure live data sent straight to the cloud
  • Instant SMS alerts for temperature alarms
  • Internal memory of up to 18,500 samples when outside range of access point (64 days based on 5 minute samples)
  • 10-year battery life
  • 24/7 monitoring- access data whenever, wherever on any smart device
  • Reports generated at the click of a button
  • Cost effective, robust and waterproof logger
  • Operating internal sensor temperature range is -40°C to +70°C

Technical Specifications:

RangeUp to 600 m / 2000 ft outdoors
Logging Capacity18,500 events with date / timestamp
Battery LifeUp to 10 years or 1 million messages
Operating range -40 °C to +70 °C
Accuracy Max.±0.10 °C (0 °C to 70 °C)
±0.15 °C (-40 °C to 0 °C
Resolution0.01 °C
Long Term Stability≤ 0.01 °C /year
Protection ClassIP67 condition: mating connector placed.
Height143 mm / 5.63 in
Width35 mm / 1.38 in
Depth25 mm / 0.98 in
Weight56g
Connector / interface4-pin SenseAnywhere Bus
Dimensions ConnectorØ 11.5mm x 48mm/ 0.45in x 1.89in
Protection ClassIP62
Operating range -40 °C to +70 °C
AccuracyMax. ±0.10°C (0°C to 70°C)
Max. ±0.15°C (-40°C to 0°C)
Resolution0.01 °C
Long Term Stability≤ 0.01 °C /year
Connector / interface4-pin SenseAnywhere Bus
Dimensions ConnectorØ 11.5mm x 48mm/ 0.45in x 1.89in
Protection ClassIP62
Operating range -40 °C to +70 °C
AccuracyMax. ±0.10°C (0°C to 70°C)
Max. ±0.15°C (-40°C to 0°C)
Resolution0.01 °C
Long Term Stability≤ 0.01 °C /year
Humidity Range0-99% non-condensing
Humidity AccuracyTyp. ±2% RH Max. ±3% RH (0-80% RH), Max. ±4.5% RH (80-100% RH)
Humidity Resolution0.1%
Long Term Humidity Stability≤ 0.25% RH / year (Prolonged use at extreme temperature and/or humidity levels may result in a larger RH% drift).
Connector / interface4-pin SenseAnywhere Bus
Dimensions ConnectorØ 11.5mm / 0.45in
Cable2-wire, Ø 3mm TPU cable, 2m long, 2-wire stripped end, 8mm tinned
Protection ClassIP67 when connected to AiroSensor
Operating range -40 °C to +70 °C
Input Impedance49.9Ohm
Max Current±24mA
ESD Protection±2KV
Measurement Range-20mA to +20mA
Resolution0,001mA (18 bit ADC)
Accuracy± (0.003 + 0.03% of reading)mA
Temperature Drift< 0.35µA/°C
Reverse Polarity ProtectionYes
Connector / interface4-pin SenseAnywhere Bus
Dimensions ConnectorØ 11.5mm / 0.45in
Cable2-wire, Ø 3mm TPU cable, 2m long, 2-wire stripped end, 8mm tinned
Protection ClassIP67 when connected to AiroSensor
Operating range -40 °C to +70 °C
Input Impedance22.2kOhm
Max Voltage±15V
ESD Protection±2KV
Measurement Range-10V to +10V
Resolution0,001V (18 bit ADC)
Accuracy± (0.003 + 0.03% of reading)V
Temperature Drift< 0.15µV/°C
Reverse Polarity ProtectionYes